Description
Parameters and specifications
Input channel:
Four 20 mA DC analog input channels
Accuracy (including linearity) of each channel: ±0.03% of the range
Input signal A/D conversion: Each channel uses a separate Sigma-Delta converter
Input channel impedance: nominal 61.5 Ω
Integral cycle: Software configurable
Common mode rejection (50 or 60 Hz) : >100 dB
Normal mode suppression (50 or 60 Hz) : >95 dB
Output channel:
Four 20 mA DC analog output channels
Accuracy (including linearity) : ±0.03% of the range
Accuracy temperature coefficient: ±50 ppm/ºC
Output load: Maximum 750 Ω
Output processing delay: 30 ms Max
Resolution: 13 bits
Other parameters:
Terminal Component (TA) : Used to locally or remotely connect onsite cables to the FBM204
DPIDA control block support for fast control loop
Electrical compatibility with standard HART signals
With Sigma-Delta data conversion, new analog input readings are provided every 25 milliseconds and configurable integration cycles are provided to eliminate noise and power line frequency
trait
High precision: High precision is achieved through Sigma-Delta data conversion technology
Electrical isolation: Each input and output channel is electrically isolated to provide greater safety and reliability
Rugged design: Suitable for cabinets in G3 (harsh) environments, with a robust extruded aluminum housing
Redundant communication: Supports redundant 2 Mbps module fieldbus to ensure the reliability and stability of communication
Reviews